Benefits of using LT Capacitors over HT Capacitors

Benefits of using LT Capacitors over HT Capacitors
Updated: | 6 min read

Technical Articles

Power factor compensation can be provided on either LT or HT side of the distribution transformer for the loads at the LT side. Often compensation is done on the HT side as the electricity board measures power factor on HT side for penalty calculation. Also, HT capacitors involve low initial investment as compared to LT capacitors. However, compensation achieved by HT capacitors does not provide the benefits offered by the use of LT capacitors, as discussed in this article.


Consider two cases with compensation provided on HT & LT side respectively as shown in figure1 & 2.

HT & LT Side

As seen in fig 1, with the capacitor connected on the HT side, the compensated reactive power flow through the transformer does not reduce and hence there is no change in current flow. Although the HT side power factor is improved, the LT side power factor remains same. However, as seen in fig 2, connecting capacitor on LT side reduces the reactive power flow through the transformer and we get improved power factor and reduced current flow on both LT and HT sides.

1. Reduction in transformer copper losses:

Consider a load of 1200 kW connected to a transformer of 2000 kVA. The typical full-load copper losses in a 2000 kVA transformer are 25000W.


When compensation is provided on HT side, operating power factor of the transformer is 0.75 (same as uncompensated), denoted by cosØ1.


When compensation is provided on LT side, operating power factor of the transformer is 0.98 (compensated), denoted by cosØ2


Power Saving = WK * (1/COSØ1 - 1/COSØ2)


Where,

Wf = Full Load Copper Losses = 25000 W


K = Load in kW / kVA rating of transformer = 0.6


Thus, LT compensation provides monthly saving of ₹ 20,278/- for a 2000 kVA transformer. Additionally, the operating temperature of the transformer is relatively less because of reduced copper losses. Hence, apart from monetary benefits, LT compensation also ensures longer life of the transformer.

2. Capacity release in transformer:

Consider a 2000 kVA transformer connected to a load.


Case 1: When compensation is provided on the HT Side, operating PF of transformer = 0.75 Maximum load that can be connected = 2000 * 0.75 = 1500 kW


Case 2: When compensation is provided on LT side, operating PF of transformer = 0.98 Maximum load that can be connected = 2000 * 0.98 = 1960 kW


Additional load that can be connected under the same transformer = 460 kW


LT compensation allows release of capacity of 460 kW with the same transformer. Thus, additional load can be easily connected to the system without any additional investments in new transformers.

3. Optimized main incomer switchgear rating:

LT side capacitor, when connected after the main incomer reduces the current drawn by the same set of loads. Hence incomer switchgear rating can be optimized and the investment cost of the main incomer can be reduced.


Apart from those mentioned above, LT compensation also offers other advantages, such as

  • Maintenance of LT capacitors and panels is easier and does not require complex safety measures.
  • Spares and accessories for the same are easily available and relatively cheaper.


Thus, for a factory with all LT loads, power factor compensation with LT capacitors proves to be a better option, with its relatively lesser payback period.

About the Author

author

Abhinav L Purkar,

Manager Product Management & Marketing (PMM)

Abhinav Purkar is a Product Management, Marketing, and Application Engineering professional with over 10 years of experience in the Power Quality domain. He has extensive expertise in power quality analysis, harmonic mitigation, reactive power compensation, energy efficiency, and electrical system optimization, helping customers improve system reliability and operational performance. With proven experience in product lifecycle management, market development, portfolio growth, and go-to-market strategy, Abhinav has successfully driven initiatives that enhance customer value and strengthen market presence. His strong technical foundation, combined with strategic business acumen, enables him to bridge the gap between customer requirements and innovative product offerings.