The most common loads in industry are primarily inductive i.e. comprising motors and induction type devices. Higher percentage of inductive loads leads to lagging power factor in the power system. The disadvantages associated with lagging power factor viz. increase in current for same power output requires larger size conductor and associated devices like switchgears and transformers. In order to eliminate these disadvantages, capacitors are commonly used in most of the installations. The capacitor draws leading power factor and hence used to compensate the lagging power factor drawn by inductive devices.
As the load of the industrial unit is variable, some capacitor banks are permanently connected while others are switched on and off according to the requirement of the system. The device used to switch on the capacitor bank automatically according to the requirement of the system is called Automatic Power Factor Controller (APFC).
Switching of capacitors poses certain challenges in the electrical system. When these capacitors are energized, over-currents of high amplitude (up to 200 In) and high frequencies occur during the transient period (1 to 2 ms).
The amplitude of these current peaks, also known as "peak inrush current", depends on the following factors:
There are 2 types of power factor correction: fixed or automatic.
Fixed power factor correction consists of inserting a capacitor bank in parallel to the system. The capacitor bank can be either identical or different unit capacitors. The bank is energized by a contactor that simultaneously supplies to all the capacitors (a single step). The inrush current peak, in the case of fixed correction, can reach as high as 30 times the nominal current of the capacitor bank.
An automatic power factor correction system, on the other hand, consists of several capacitor banks of identical or different kVAR (several steps), energized separately according to the value of the power factor to be corrected. An electronic controller automatically determines the kVAR of the steps to be energized and activates the relevant switching device. The inrush current peak, in the case of automatic correction, depends on the both, the capacitors already on duty and the capacitor bank being switched on. Peak inrush current in this case can reach 200 times the nominal current of the step to be energized.
The calculation of peak inrush current varies according to the arrangement of capacitor units used for power factor correction
Case-I: fixed capacitor bank switching
A fixed capacitor is connected in parallel to the system to be compensated as shown in figure below:
The in-rush current peak
Where, Q = Capacitor Bank Rating in kVAr
Leq = Per Phase Inductance of Electrical Apparatus and Connections in μH (Transformer inductance + Inductance of Electrical Apparatus + Inductance of Electrical connections)
1457 = Constant calculated for 50 Hz.
= √ (10e9) / (3 π f)
Assuming an example of 100 kVA transformer with 415 V a.c., 50 Hz output voltage and 5% short-circuit voltage; the transformer inductance per phase is calculated
Lt = 5 * 415 * 415 / (31.4 * 100)
Where 31.4 = constant for 50 Hz = 274. 24 μH
Inductance of Electrical Apparatus is provided by the manufacturer. In case the data is not provided by the manufacturer, the value of 0.5 μH / phase can be considered for calculation purpose.
The inductance value of the electrical connection i.e. the cables is provided by the manufacturer. Various manufacturers provide cable inductance on their websites. This data can be used for calculation purpose.
The capacitor banks of equal ratings are connected across the system as per the kVAR requirement of the system. Here the first capacitor unit when switched on, the peak inrush current calculation will be similar to Case-I. This is because when the first capacitor unit is switched on, the current flowing through this unit is limited by the system impedance, which comprises of reactance of transformer, reactance of electrical apparatus and reactance of electrical connections.
When the subsequent capacitor banks are switched on, peak inrush currents are much higher in the circuit. This is because the capacitor banks that are already connected to the system try to discharge through the recently switched capacitor unit. The reactance between two capacitor banks is only the reactance of cable (very small in length) and reactance of switching devices. The total reactance between two capacitor banks is very small and therefore the peak inrush current is very high. The calculation of peak inrush current from second capacitor bank onwards is calculated as:
Where,
Qn = Capacitor kVAr Rating in step n (here all stages have same kVAr rating)
Leq = Per Phase Inductance value of Electrical apparatus & Electrical connections for step n.
1457 = Constant calculated for 50 Hz, as shown in earlier calculations.
The capacitor banks of unequal ratings are connected across the system as per the kVAR requirement of the system. Any rating capacitor unit can be switched on-off as per the requirement of the system. Here the first capacitor unit when switched on, the peak inrush current calculation will be similar to Case-I.
When the subsequent capacitor banks are switched on, peak inrush current is much higher. The calculation of peak inrush current from second capacitor bank onwards is calculated as:
Where, Qn = Capacitor kVAr Rating in step n
Ln = Per Phase Inductance value of Electrical apparatus & Electrical
Connections for step n.
1457 = Constant calculated for 50 Hz, as shown in earlier calculations.
High peak inrush current as explained above can have following ill-effect in the installation:
It is necessary to limit the peak inrush current to the value that will not cause any harm to all the devices connected to the system especially switching and protective devices.
There are two type of current limiting mechanisms popularly used to limit the peak inrush current to safe limit:
The capacitor duty contactors are the contactors with special type of arrangement. A fixed value of resistors called pre-insertion resistors are placed in the contactors in such a way that the resistors come in series with the contactors during switching. These resistors are disconnected from the circuit after a few milliseconds. This resistor limits the inrush current to safe limit. However, capacitor duty contactors are popularly used up to certain steps of capacitor bank only. In case the total number of steps is more, possibility of burning of pre-insertion resistor can be there.
The use of series inductor is another safe and reliable method of switching capacitor bank. The inductor when connected in series, the total reactance of the system increases thus reducing the peak inrush current.
A common practical method for making additional inductances is to add additional inductances, simply by winding the cables designed to be connected to the capacitor bank, onto a cylinder. An electrical conductor (cable) wound with joining turns on a cylinder of a diameter (d) as shown in figure below:
Forms an inductance coil whose inductance is equal to:
Where
L: self-inductance in H
N: number of circular turns
a, b, c, d, r: dimensions in m
The selection of appropriate switching and protective device for such application is based on two criterions
A capacitor circuit is always prone to higher percentage of harmonic currents. The presence of harmonics and the network's voltage tolerance lead to a current, estimated to be 1.3 times the nominal current In of the capacitor, permanently circulating in the circuit.
Taking into account the manufacturing tolerances, the exact current drawn by a capacitor can reach 1.15 times its nominal rated current. Standard IEC 831- 1 Edition 04/97 specifies that the contactor / switching device must therefore have a minimum thermal current Ie of:
Ie = 1.3 x 1.15 x In = 1.5 In
Hence the switching & protective devices connected in a capacitor circuit must have continuous rating of 150% of the rated capacitor current.
As explained earlier, the selection of protective device is very important for capacitor switching application due to the possibility of very high peak inrush current.
In the applications where devices like MCCBs/MCBs are used for protection, there is a high probability of nuisance tripping during switching ON. This is because MCCBs & MCBs are peak current sensing devices & can trip if the inrush current exceeds the instantaneous trip current setting. Hence it is necessary to limit the peak inrush current below the magnetic threshold current for switching and protection device.
During study of capacitor switching phenomena, it was observed that the duration of peak inrush current is very low (in micro seconds). While this time is not sufficient to trip the MCCB, it’s contacts can repel open (due to current limiting design), leading to unwanted higher contact erosion. The molten contacts when reclose may also cause welding of the contacts.
The above problem is less likely to happen in case fuse is used for protection. Fuse works on energy principle & less sensitive to current peaks in the system. The total energy within the inrush current is very low (generally lower than the fusing energy of the fuse). Thus the system works fine.
It is evident that uncontrolled (without limiting device) switching of capacitor bank can cause tripping/open circuit/contact welding in case of MCCB. This will also result in premature failures of capacitors.
Hence adequate care needs to be taken while selecting switching & protection devices for capacitor applications. It is always advised to limit the switching inrush current within safe limits using appropriate options as described in the article.
Maya Pai,
Deputy General Manager - Product Management & MarketingMaya Pai is a seasoned Product Management and Marketing professional with over 10 years of experience in the electrical industry, specializing in low-voltage switchgear and circuit protection solutions. Her expertise lies in Molded Case Circuit Breakers (MCCBs) and DC Portfolio management, encompassing product strategy, portfolio development, market analysis, and customer-centric innovation. She has worked extensively across the product lifecycle, translating evolving market and application requirements into competitive and reliable solutions for power distribution systems. Her experience spans conventional AC protection as well as emerging DC applications, supporting the growing demand for energy storage, renewable energy integration, EV infrastructure, and industrial DC power systems. Through her work and writing, she shares insights on switchgear technologies, circuit protection, DC systems, and the future of efficient, safe, and resilient power distribution.