Contactor coils were mostly designed for 50 Hz supply for the international market. In Therefore, now 60 Hz rating frequency as Indian power system typically operates at 50Hz are now marked on most of our coils as shown in the table However we do get requirement for 60 Hz coils are required below.
| Range | Rated Coil Voltage | % Pick up band @50 Hz | % Pick up band @60 Hz |
|---|---|---|---|
| MNX 9 - 32 | 110 V 50/60 Hz | 65-120 | 85-120 |
| 220 V 50/60 Hz | |||
| 240 V 50/60 Hz | |||
| 415 V 50/60 Hz | |||
| MNX 40 - 650 | 110 V 50 Hz | 80-110 | 80-110 |
| 132 V 60 Hz | |||
| 220 V 50 Hz | |||
| 264 V 60 Hz | |||
| 240 V 50 Hz | |||
| 288 V 60 Hz | |||
| 415 V 50 Hz | |||
| 498 V 60 Hz |
| Range | Rated Coil Voltage | % Pick up band @50 Hz | % Pick up band @60 Hz |
|---|---|---|---|
| MNX 01 - 04 | 110 V 50/60 Hz | 55-120 | 75-120 |
| 220 V 50/60 Hz | |||
| 240 V 50/60 Hz | |||
| 415 V 50/60 Hz | |||
| MNX 11 - 47 | 110 V 50 Hz | 80-110 | 80-110 |
| 132 V 60 Hz | |||
| 220 V 50 Hz | |||
| 264 V 60 Hz | |||
| 240 V 50 Hz | |||
| 288 V 60 Hz | |||
| 415 V 50 Hz | |||
| 498 V 60 Hz |
| Range | Rated Coil Voltage | % Pick up band @50 Hz | % Pick up band @60 Hz |
|---|---|---|---|
| MO 9 - 45 | 24 V 50/60 Hz | 65-110 | 85-110 |
| 42 V 50/60 Hz | |||
| 48 V 50/60 Hz | |||
| 110 V 50/60 Hz | |||
| 220 V 50/60 Hz | |||
| 240 V 50/60 Hz | |||
| 320 V 50/60 Hz | |||
| 360 V 50/60 Hz | |||
| 380 V 50/60 Hz | |||
| 415 V 50/60 Hz | |||
| 525 V 50/60 Hz |
| Range | Rated Coil Voltage | % Pick up band @50 Hz | % Pick up band @60 Hz |
|---|---|---|---|
| MO 50 - 300 | 24 V 50/60 Hz | 75-110 | 85-110 |
| 42 V 50/60 Hz | |||
| 48 V 50/60 Hz | |||
| 110 V 50/60 Hz | |||
| 220 V 50/60 Hz | |||
| 240 V 50/60 Hz | |||
| 320 V 50/60 Hz | |||
| 360 V 50/60 Hz | |||
| 380 V 50/60 Hz | |||
| 415 V 50/60 Hz | |||
| 525 V 50/60 Hz |
Sandeep Pawar,
General Manager - Product ManagementElectrical Engineer with over 20 years of experience in Product Management and Application Engineering for Protection Relays, Power Quality Solutions, and Intelligent Motor Control Centres (MCCs). Possesses strong expertise in LV and MV power system protection schemes, motor protection, monitoring, and control applications. Well-versed in both conventional and intelligent motor management systems, with extensive knowledge of protection, control, and condition monitoring solutions.