It's a known fact that harmonics cause over loading of power capacitors and consequently reduce the life of power capacitors. Normally lot of emphasis is given only to %THD for assessing the harmonics level while the frequency spectrum (5th, 7th, 11th, 13th and so on) of the harmonics are not given due importance. The over-current (and hence the stress on the capacitors) will not only depend on the %THD value but also on the magnitude of individual harmonics, which can be clearly seen in the frequency spectrum. Following calculations prove the above statement. 

Case 1

Assumptions:

  1. VTHD : 25%
  2. Harmonic frequencies considered: 5th (250 Hz), 7th (350 Hz)
  3. V5=20%V1 and V7=15%V1
  4. All other harmonic frequencies are negligible
  5. The capacitors are delta connected hence will not provide a path for the third harmonic to flow

Important Formulae


Superposition Theorem

where XC is the capacitive reactance, f is the frequency, C is the capacitance IC=VC / XC, where IC is the capacitive current, VC is the voltage across the capacitor and XC is the capacitive reactance


VTHD = √Σ(Vi)2 / V1), where i=3 to 99

Calculations

Using the superposition theorem, we can calculate the current contribution of individual harmonic voltages.

Superposition Theorem

Case 2

Assumptions:


  1. VTHD : 25%
  2. Harmonic frequencies considered: 5th (250 Hz), 7th (350 Hz), 11th (550 Hz), 13th (650 Hz)
  3. V5 =18%V1, V7 =15%V1, V11 =8%V1 and V13 =4%V1
Harmonic frequencies

Net current, I =2 I1 > (2)


Thus, in the above two cases, even the THD value remains same (25%), the net rms current (ref. Eq 1 and Eq 2) value is different depending upon the spectral values. 


Hence THD value and detailed information of the frequency spectrum are necessary to predict the capacitor over-current. Harmonics study is the best way to get the frequency spectrum details and hence the exact over current value can be calculated.

About the Author

author

Abhinav L Purkar,

Manager Product Management & Marketing (PMM)

Abhinav Purkar is a Product Management, Marketing, and Application Engineering professional with over 10 years of experience in the Power Quality domain. He has extensive expertise in power quality analysis, harmonic mitigation, reactive power compensation, energy efficiency, and electrical system optimization, helping customers improve system reliability and operational performance. With proven experience in product lifecycle management, market development, portfolio growth, and go-to-market strategy, Abhinav has successfully driven initiatives that enhance customer value and strengthen market presence. His strong technical foundation, combined with strategic business acumen, enables him to bridge the gap between customer requirements and innovative product offerings.