Technical Articles
UN-CO module is used for remote closing and opening operation of MCCB/ACB through Modbus RTU protocol and uploading status of breakers to Modbus master. This module is used for controlling operation of two breakers. Each module connected to communication bus is identified by an address code programmable from 1 to 16. RS485 converter module is necessary for converting RS485 to RS232.
1. Physical dimensions: same as UN-PS module. Terminals of UN-PS module will be used for wiring for various connections.
2. Power supply: UN-CO Module will be powered from UN-PS Module. Current requirement of UN-CO module will be 250mA at 24V dc. 24V dc available at customer’s place can be used but EMI/EMC compatibility should be 4.0kV. UN-PS module is recommended for UN-CO because assumption made is that UN-PS has 4.5kV differential as well as common mode EMI/EMC compatibility.
3. Digital input1 indicating the breaker status i.e. when ACTIVATED indicates that breaker is close (MCCB1 Aux NO contact to be used for sensing ON state). Digital input2 indicating the breaker status i.e. when ACTIVATED indicates that breaker is open (MCCB1 Aux NC contact to be used for sensing OFF state which is optional).
Similarly, Digital input3 and Digital input4 will be used to indicate close and open condition of MCCB2 respectively. These four contacts are potential free contacts.
4. Open and Close commands through Stored Energy EOMs for each breaker. These four contacts are potential free contacts.
Contact rating: 250V AC / 8A.
5. LED indication:
6. Communication Parameters are as follows:
7. A four-way DIP switch is used for address selection of the devices. This makes it possible to connect 16 such devices for controlling ON/OFF operations of 32 MCCBs.
Terminal Details:
The Communication host shall send the query as per the memory map which will be provided. The UN-CO module will process the query and respond accordingly.
In case the customer wants to develop their own communication software L&T provides the memory map of UN-CO Module.
Annexure1: Memory Map
Annexure2: Connection Diagram
| READ ONLY PARAMETERS : FUNCTION CODE 4 | ||||||
| Sr. No. | Hex Add. | PARAMETERS | WORD | |||
| 1 | 0x7531 OR 30,001 | Status of MCCB1 and MCCB2 (Upper byte is 0x00) Lower byte split-up | 1 | |||
| D7-D6 MCCB1 ON | D5-D4 MCCB1 OFF | D3-D2 MCCB2 ON | D1-D0 MCCB1 OFF | |||
| FORCE COIL: FUNCTION CODE 05 | ||||||
| Slave Id. | Data Coil No (MCCB No) | PARAMETERS | WORD | |||
| DIP Switch | MCCB1 (0x0001) | MCCB 1 (0x0000) open, (0xff00) close | 1 | |||
| DIP Switch | MCCB2 (0x0003) | MCCB 2 (0x0000) open, (0xff00) close | 1 | |||
| EXCEPTIONS | ||||||
| Sr. No. | Error | Description | ||||
| 1 | Data Error | If there is query which asks for more or less number of data then It will give data error (0x03) | ||||
| 2 | Illegal Address | If there is query which asks for data which is not available (i.e. not mapped) then It will give Address error (0x02) | ||||
| 3 | Illegal Function Code | If there is query which has wrong function code then It will give Function code error (0x01) | ||||
Maya Pai,
Deputy General Manager - Product Management & MarketingMaya Pai is a seasoned Product Management and Marketing professional with over 10 years of experience in the electrical industry, specializing in low-voltage switchgear and circuit protection solutions. Her expertise lies in Molded Case Circuit Breakers (MCCBs) and DC Portfolio management, encompassing product strategy, portfolio development, market analysis, and customer-centric innovation. She has worked extensively across the product lifecycle, translating evolving market and application requirements into competitive and reliable solutions for power distribution systems. Her experience spans conventional AC protection as well as emerging DC applications, supporting the growing demand for energy storage, renewable energy integration, EV infrastructure, and industrial DC power systems. Through her work and writing, she shares insights on switchgear technologies, circuit protection, DC systems, and the future of efficient, safe, and resilient power distribution.
Assistance Required?
Select an option to Contact Us