Crane duty application is an example of AC-4 utilization category where the contactor is subjected to severe inching operations. This is the case when the motors are used in DOL configuration without Variable frequency drives for speed and torque control. As such, Crane duty application is one of the most severe applications greatly straining the contactor.
In the earlier days Slip ring motors dominated crane duty applications. However nowadays we find both squirrel cage as well as slip ring induction motors being used for crane applications. With advent of Variable frequency drives providing efficient Speed and torque control, the application becomes less severe for the contactors. This is because all the switching needs are taken care by the VFD and the contactor can be selected as per AC-I utilization category. However VFD is a costly proposition and in price driven markets like India, many still prefer to use contactors in conventional configuration for their crane duty applications.
This application notes explains how one should go about selecting the contactors when VFD is not into the picture. In such a scenario the contactor is expected to undergo severe inching operations and hence life of the contactor becomes paramount selection criteria.
As emphasized above, the life of the contactor is an important parameter and one must be clear about the life One expects from the contactors when used for crane duty applications. Most of the crane duty manufacturers would expect a certain fixed amount of life and this would then guide their contactor selection.
Power contactors usually have an AC-4 rating mentioned in the product catalogue. However the electrical life given in Life curves is also an important criterion which influences contactor selection.
For example,
Consider M032 Power Contactor. The rated AC-4 current of M032 is 32A.
The Electrical life of MO 32 at 32A AC-4 is 50000. When a 32A contactor is used for 32AAC-4 application, one gets an operation life of 50000 operating cycles. If the contactor does approximately 500 switching cycles per week then the contactor will last for a period of 50000/500 = 100 weeks i.e. roughly 2 years.
As emphasized above, the life of the contactor is an important parameter and one must be clear about the life One expects from the contactors when used for crane duty applications. Most of the crane duty manufacturers would expect a certain fixed amount of life and this would then guide their contactor selection.
Here the user must be aware of the approximate switching frequency that the contactors will be subjected too in a given day and then based on the life he desires he can back calculate to arrive at contactor rating. For example, User Specifications are given below,
Referring the electrical life curves, the contactor that gives a life of 0.35 million at 30A AC-4 current is MO 95. Hence for this requirement MO 95 is the correct contactor selection.
If one directly selects the contactor as per rated current without considering the electrical life then the electrical life at 30 A AC-4 will be approximately 57000. Hence the contactor will last only for (57000/300) 190 days which is much lower than desired life.
Always consider the rated current and desired Electrical life and based on that arrive at the contactor rating through Electrical life curves.
Most of the times users are not aware of the exact operating cycles the contactor may be subjected too and hence they can refer a standard benchmark of 200000 operating cycles.
Below is the selection table of contactors for 200000 operating cycles
| Contactor | Rated Current (A) for 200000 operating cycles at AC-4 415V 50Hz |
|---|---|
| MO 9 | 5.3 |
| MO 12 | 7.3 |
| MO 18 | 9 |
| MO 25 | 16 |
| MO 32 | 16 |
| MO 40 | 18 |
| MO 45 | 19 |
| MO 50 | 23 |
| MO 60 | 25 |
| MO 70 | 27 |
For example, if one wants 200000 operating cycles for the rated current of 9A AC-4 then contactor selected should be MO 18 or above
This method of contactor selection is much simpler and must be employed when one expects a fixed electrical life of 200000 operating cycles which is more than sufficient for crane duty applications. If one desires a higher life than 200000 then one can derate the contactors by selecting one or two ratings higher or lower if lower life is acceptable and then verify the selection through Electrical life curves.
| Contactor | Rated Current (A) for 200000 operating cycles |
|---|---|
| MO 80 | 34 |
| MO 95 | 37 |
| MO 110 | 41 |
| MO 140 | 60 |
| MO 185 | 75 |
| MO 225 | 85 |
| MO 250 | 100 |
| MO 300 | 130 |
Selection Chart for Slip Ring Induction Motors for Crane Duty Applications
| Stator duty - 415V 50Hz (10 min cycle duration) | Rotor duty: Delta Connected (10 Min Cycle duration) | Max rotor voltage | |||||||
| Duty Factor | 20% | 40% | 60% | 20% | 40% | 60% | Starting | Plugging | Speed Control |
| MO 9 | 12A | 10.5A | 9.5A | 40A | 35A | 30A | 1100V | 415V | 550V |
| MO 12 | 17A | 15A | 13A | 51A | 42A | 39A | 1100V | 415V | 550V |
| MO 18 | 23A | 19.5A | 17.5A | 63A | 54A | 47A | 1100V | 415V | 550V |
| MO 25 | 32A | 27A | 23A | 93A | 80A | 70A | 1100V | 415V | 550V |
| MO 32 | 45A | 39A | 34A | 102A | 87A | 76A | 1100V | 415V | 550V |
| MO 40 | 50A | 42A | 37A | 115A | 95A | 86A | 1100V | 415V | 550V |
| MO 45 | 50A | 42A | 37A | 115A | 95A | 86A | 1100V | 415V | 550V |
| MO 50 | 63A | 54A | 48A | 140A | 120A | 110A | 1100V | 415V | 550V |
| MO 60 | 85A | 73A | 65A | 180A | 155A | 140A | 1100V | 415V | 550V |
| MO 70 | 110A | 95A | 85A | 215A | 185A | 163A | 1100V | 415V | 550V |
| MO 80 | 110A | 95A | 85A | 215A | 185A | 163A | 1100V | 415V | 550V |
| MO 95 | 165A | 135A | 120A | 260A | 230A | 200A | 2200V | 415V | 690V |
| MO 110 | 185A | 150A | 135A | 300A | 260A | 230A | 2200V | 415V | 690V |
| MO 140 | 210A | 210A | 175A | 315A | 315A | 262A | 2000V | 415V | 600V |
| MO 185 | 288A | 288A | 228A | 416A | 416A | 343A | 2000V | 415V | 600V |
| MO 225 | 331A | 331A | 281A | 505A | 505A | 417A | 2000V | 415V | 600V |
| MO 250 | 332A | 332A | 282A | 506A | 506A | 432A | 2000V | 415V | 600V |
| MO 300 | 407A | 407A | 340A | 610A | 610A | 510A | 2000V | 415V | 600V |
Sandeep Pawar,
General Manager - Product ManagementElectrical Engineer with over 20 years of experience in Product Management and Application Engineering for Protection Relays, Power Quality Solutions, and Intelligent Motor Control Centres (MCCs). Possesses strong expertise in LV and MV power system protection schemes, motor protection, monitoring, and control applications. Well-versed in both conventional and intelligent motor management systems, with extensive knowledge of protection, control, and condition monitoring solutions.