Technical Articles
Circuit breaker can break two faults of the claimed value and can make one fault of the claimed value, after this breaker is not tested for anything and it is advisable to replace the breaker.
O-CO
For e.g. consider a breaker with 250A as rated current and 50kA as ultimate short circuit breaking capacity, if two faults of 50kA occur then after that breaker must be replaced with a new breaker.
In simpler terms, if Icu would have been a person lifting weight, then Icu can lift 2 laps of maximum weight, after which he cannot lift anything.
Icu = 2 laps of maximum weight only
Circuit breaker can break three faults of the claimed value and make two faults of the claimed value. After this, breaker can make, carry and break normal current and can give overload protection, but it cannot clear short circuit fault. Hence, this is the most important short circuit breaking capacity of breaker.
O-CO-CO
For e.g. consider a breaker with 250A as rated current and 50kA as service short circuit breaking capacity, if three faults of 50kA occur then after that breaker can still make, break and carry 250A and provide overload protection unless it is replaced by new breaker. It reduces downtime of industries and hence the financial losses.
In simpler terms, if Ics would have been a person lifting weight, then Ics can lift 3 laps of maximum weight and after that lighter weights.
Ics = 3 laps of maximum weight and lighter weights
Sourav Dasmodak,
Product Management & Marketing (Powergear - ACB)Product Owner of Air Circuit Breaker (ACB) of Lauritz Knudsen for Domestic & International Market. I can talk to you about Electrical Products' Sales, Business Development, Market Expansion, Cracking Critical Strategic Account, handling Key Account & of course how to develop & motivate Channels along with the organizational growth. Having near about one and a half decade of experience across the country with major electrical manufacturers (Top 4).
Assistance Required?
Select an option to Contact Us