A Circuit Breaker is an automatically operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. According to Standards, a circuit breaker is a mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time and breaking currents under specified abnormal circuit conditions such as those of short circuit.
A moulded case circuit breaker is compact by its name. Hence by virtue of compactness, it is needless to say that adequate measures should be taken while terminating these to the links / bus-bars.
In context of termination of MCCBs, spreaders play a significant role. It not only makes room for suitable link / bus-bar termination, but ensures safe & reliable operation of MCCB and the panel also.
Now when it comes to choosing the material of spreaders and its plating, the selection should be judicious so that the same is economically viable also.
This article intends to provide safe and reliable termination guide-lines with respect to our “d-sine” range of Moulded Case Circuit Breakers and how spreaders play a vital role in it.
This section deals with choosing the correct bus-bar size for proper termination of MCCBs along with selecting proper spreader material for lesser temperature rise. Termination of MCCBs had always been a critical issue for the panel- builders as well as the end-users since it depends on several issues as follows:
• Ampere rating of MCCB
As the ampere rating increases the bus-bar size also increases.
• Bus-bar material
✓ Al bus-bar (current density = 0.8-1 A/mm2)
✓ Cu bus-bar (current density = 1.2-1.6 A/mm2)
• Magnetic forces
Due to parallel current carrying bus-bars, magnetic forces are developed. While designing bus-bar size these attractive & repulsive forces are also needed to be taken care of.
• Fault level of the system
One of the most important factors on which bus-bar size depends upon, is the fault level of the system. When a fault occurs it is generally of kA level. Hence even if our MCCB clears fault within 10ms, the total energy generated during fault is huge. The bus-bars thus need to be designed to withstand this high amount of energy & dissipate the same.
We know energy generated
H = m*s*(T2-T1)
Where,
m = Mass of the bus-bar
s = Specific heat capacity of the bus-bar material
T2-T1 = Temperature rise of the bus-bar
As we know, specific heat capacity is an intrinsic property of the material. Hence it is constant for a particular material.
To make the heat dissipation process easier the temperature rise of the bus-bar must be limited in a controlled manner. To lessen the temperature rise of the bus-bar, its mass has to be increased.
Now we have to judiciously choose the bus-bar size so that the temp rise remains within limits.
• Ambient temperature of the Panel
Ambient temperature is a significant factor on which panel design depends upon. The more the ambient temp the less the temp difference leading to larger size of bus-bars.
Let us now have the table given in IEC-60947-1 of standard size of copper conductors for test currents up to 400A & standard copper bars beyond 400A up to 3150A.
| Table 9 - Test copper conductors for test currents up to 400 A inclusive* | |||
|---|---|---|---|
| Range of test current 1 | Conductor size 2, 3, 4 | ||
| A | mm2 | AWG/MCM | |
| 0 | 8 | 1,0 | 18 |
| 8 | 12 | 1,5 | 16 |
| 12 | 15 | 2,5 | 14 |
| 15 | 20 | 2,5 | 12 |
| 20 | 25 | 4,0 | 10 |
| 25 | 32 | 6,0 | 10 |
| 32 | 50 | 10 | 8 |
| 50 | 65 | 16 | 6 |
| 65 | 85 | 25 | 4 |
| 85 | 100 | 35 | 3 |
| 100 | 115 | 35 | 2 |
| 115 | 130 | 50 | 1 |
| 130 | 150 | 50 | 0 |
| 150 | 175 | 70 | 00 |
| 200 | 225 | 95 | 0000 |
| 225 | 250 | 120 | 250 |
| 250 | 275 | 150 | 300 |
| 275 | 300 | 185 | 350 |
| 300 | 350 | 185 | 400 |
| 350 | 400 | 240 | 500 |
| * See notes following table 11. | |||
| Range of test current 1 A | Conductors 2,3,4 | ||||
| Metric | MCM | ||||
| Number | Size mm2 | Number | Size MCM | ||
| 400 | 500 | 2 | 150 | 2 | 250 |
| 500 | 630 | 2 | 185 | 2 | 350 |
| 630 | 800 | 2 | 240 | 3 | 300 |
| * See notes following table 11. | |||||
| Range of test current 1 | Copper bars 2,3,4,5,6 | |||
| Number | Dimensions mm | Dimensions inches | ||
| 400 | 500 | 2 | 30 * 5 | 1 * 0,250 |
| 500 | 630 | 2 | 40 * 5 | 1,25 * 0,250 |
| 600 | 800 | 2 | 50 * 5 | 1,5 * 0,250 |
| 800 | 1000 | 2 | 60 * 5 | 2 * 0,250 |
| 1000 | 1250 | 2 | 80 * 5 | 2,5 * 0,250 |
| 1250 | 1600 | 2 | 100 * 5 | 3 * 0,250 |
| 1600 | 2000 | 3 | 100 * 5 | 3 * 0,250 |
| 2000 | 2500 | 4 | 100 * 5 | 3 * 0,250 |
| 2500 | 3150 | 3 | 100 * 10 | 6 * 0,250 |
| NOTES to tables 9, 10 and 11 | ||||
| NOTE 1 The value of test current shall be greater than the first value in the first column and less than or equal to the second value in that column. | ||||
| NOTE 2 For convenience of testing and with the manufacturer's consent, smaller conductors than those given for a stated test current may be used. | ||||
| NOTE 3 The tables give alternative sizes for conductors in the metric and AWG/MCM system and for bars in millimetres and inches. Comparison between AWG/MCM and metric sizes is given in table 1. | ||||
| NOTE 4 Either of the two conductors specified for a given test current range may be used. | ||||
| NOTE 5 Bars are assumed to be arranged with their long faces vertical. Arrangements with long faces horizontal may be used if specified by the manufacturer. | ||||
| NOTE 6 Where four bars are used they shall be in two sets of two bars with not more than 100 mm between pair centres. | ||||
| Range of Test Current (A) | AC Conductor Size mm* |
| 0–8 | 1.5 |
| 8–12 | 1.5 |
| 12–15 | 2.5 |
| 15–20 | 4.0 |
| 20–25 | 6 |
| 25–32 | 10 |
| 32–50 | 16 |
| 50–65 | 25 |
| 65–85 | 35 |
| 85–100 | 50 |
| 100–115 | 50 |
| 115–130 | 70 |
| 130–150 | 70 |
| 150–175 | 95 |
| 175–200 | 150 |
| 200–225 | 150 |
| 225–250 | 185 |
| 250–275 | 240 |
| 275–300 | 240 |
| 300–350 | 240 |
| 350–400 | 300 |
NOTES
1. Connections shall be single-core, PVC insulated, aluminium cables or wires as indicated.
2. For single phase or multiphase tests the minimum length of each temporary connection from terminal to terminal or to the test supply or to a star point shall be:
| Range of Test Current | Aluminium Bars | |
| (A) | Quality | Dimensions |
| 400-500 | 2 | 32 * 8 |
| 500-630 | 2 | 40 * 8 |
| 630-800 | 2 | 50 * 8 |
| 800-I 000 | 2 | 50 * 10 |
| 1000-I 250 | 2 | 63 * 12 |
| 1 250-I C00 | 4 | 50 * 8 |
| 1 600-2 000 | 3 | 100 * 10 |
| 2 000-2 500 | 4 | 100 * 10 |
| 2 500-3 150 | 4 | 150 * 10 |
NOTES
1. The connections shall be made with matt black finished aluminium bars of the sizes stated in Table XA.
2. The minimum length of each temporary connection from terminal to terminal shall be 2 m.
| Diameter of thread mm | Tightening torque | |||
| Metric standard values | Range of diameter | I | II | III |
| 2,5 | ≤ 2,8 | 0,2 | 0,4 | 0,4 |
| 3,0 | > 2,8 up to and including 3,0 | 0,25 | 0,5 | 0,5 |
| - | > 3,0 up to and including 3,2 | 0,3 | 0,6 | 0,6 |
| 3,5 | > 3,2 up to and including 3,6 | 0,4 | 0,8 | 0,8 |
| 4,0 | > 3,6 up to and including 4,1 | 0,7 | 1,2 | 1,2 |
| 4,5 | > 4,1 up to and including 4,7 | 0,8 | 1,8 | 1,8 |
| 5 | > 4,7 up to and including 5,3 | 0,8 | 2,0 | 2,0 |
| 6 | > 5,3 up to and including 6,0 | 1,2 | 2,5 | 3,5 |
| 8 | > 6,0 up to and including 8,0 | 2,5 | 3,5 | 6,0 |
| 10 | > 8,0 up to and including 10,0 | - | 4,0 | 10,0 |
| 12 | > 10 up to and including 12 | - | - | 14,0 |
| 14 | > 12 up to and including 15 | - | - | 19,0 |
| 16 | > 15 up to and including 20 | - | - | 25,0 |
| 20 | > 20 up to and including 24 | - | - | 36,0 |
| 24 | > 24 | - | - | 50,0 |
Column I: Applies to screws without heads which, when tightened, do not protrude from the hole, and to other screws which cannot be tightened by means of a screwdriver with a blade wider than the root diameter of the screw.
Column II: Applies to nuts and screws which are tightened by means of a screwdriver.
Column III: Applies to nuts and screws which can be tightened by means other than a screwdriver.
In this section we discuss about the importance of spreaders in MCCB termination. Spreaders are a set of external accessory which are connected to the circuit breakers’ terminals. In context of Moulded Case Circuit Breakers, we recommend spreader terminals not only to enhance termination capacity, but for several other technical issues as follows:
1. Flexibility of termination
Use of spreaders gives plenty of options to panel builders to terminate the MCCB.
e.g. A DN3 400A MCCB has a max terminal capacity of 27mm, if terminated directly. Now if spreaders are used, then termination capacity is enhanced to 40mm. This gives panel builders much more flexibility in choosing link sizes ranging from 25mm to 40mm as per standard size.
2. Clearance increase, increase in pole pitch:
Use of spreader terminals increase phase-phase clearance and also the pole pitch. This increase in clearance has manifold effects on the overall system:
F = [(mu) x i1 x i2] / (2 x pi x d)
D = clearance between bus-bars
3. Ease of termination
Spreaders offer utmost ease of termination compared to direct mounting of links/bus-bars. It offers lesser tightening torque and improved electrical joint, thus helping in lesser temp rise also.
4. Increased life of the equipment
Thus we see that spreaders offer a basket of benefits to the customers and ensure safer installations for longer duration of operation.
Now that we have reinforced the fact that spreaders are a must in context of MCCB termination, proper selection of raw material of spreader terminals is the next most important factor. As spreaders being the connecting medium between the MCCB & Bus-bars, it is of utmost significance that we choose the correct spreader material so that temperature rise is within limit as described in IS/IEC – 60947 – 1:
| Table 2 – Temperature-rise limits of terminals | |
|---|---|
| Terminal Material | Temperature-rise limits 1, 3 K |
| Bare copper | 60 |
| Bare Brass | 65 |
| Tin plated copper or brass | 65 |
| Silver plated or nickel plated copper or brass | 70 |
| Other metals | 2 |
1) The use in service of connected conductors significantly smaller than those listed in tables 9 and 10 could result in higher terminals and internal part temperatures and such conductors should not be used without the manufacturer's consent since higher temperatures could lead to equipment failure.
2) Temperature-rise limits to be based on service experience or life tests but not to exceed 65 K.
3) Different values may be prescribed by product standards for different test conditions and for devices of small dimensions, but not exceeding by more than 10 K the values of this table.
| Table 7 – Temperature-rise limits for terminals and accessible parts | |
|---|---|
| Description of part a | Temperature-rise limits b K |
| Terminals for external connections | 80 |
| Manual operating means: metallic, non-metallic | 25, 35 |
| Parts intended to be touched but not hand-held: metallic, non-metallic | 40, 50 |
| Parts which need not be touched for normal operation: metallic, non-metallic | 50, 60 |
a. No value is specified for parts other than those listed but no damage should be caused to adjacent parts of insulating materials.
b. The temperature-rise limits specified are not intended to apply to a new sample, but are those applicable to the temperature-rise verifications during the appropriate test sequences specified in Clause 8.
As we can see from the table, only Copper & Brass are mentioned. Brass is an alloy of Copper and Zinc. Let us have the conductivity values of some materials that are commonly used in termination:
Ag – 6.30 x 10E7 S/m
Cu – 5.96 x 10E7 S/m
Al – 3.5 x 10E7 S/m
Sn – 0.917 x 10E7 S/m
Copper is the standard by which electrical materials are rated and conductivity ratings are expressed as a relative measurement to copper. These ratings will frequently be expressed as "28 IACS". IACS is the abbreviation for International Annealed Copper Standard and the number preceding "IACS" is the percentage of conductivity a material has relative to copper, which is considered to be 100% conductive. This does not, of course, mean that copper has no resistance (is 100% conductive in an absolute sense), but rather that it is the standard by which other materials are measured. The higher the % IACS, the more conductive the material is. This standard is based on an annealed copper wire having a density of 8.89 g/cm3, 1-meter-long, weighing 1 gram, with a resistance of 0.15328 ohms. This value is assigned 100 at 20°C (68°F) as per IACS. Armed with this knowledge it is interesting to examine the IACS conductivity values of some common materials.
| Material IACS % Conductivity | |
|---|---|
| Silver | 105% |
| Copper | 100% |
| Gold | 70% |
| Aluminum | 61% |
| Nickel | 22% |
| Zinc | 27% |
| Brass | 28% |
| Iron | 17% |
| Tin | 15% |
| Phosphor Bronze | 15% |
| Lead | 7% |
| Nickel Alum. Bronze | 7% |
| Steel | 3% to 15% |
It is needless to say that Copper is the best amongst all to use in termination considering judicious tradeoff between cost and performance.
The various ANSI standards covering metal-enclosed switchgear and circuit breakers used in this switchgear prescribe temperature rise limits for various parts of the equipment. Included are limitations for buses with plated & unplated joints in switchgear and for plated and unplated contacts and connections in circuit breakers. In all the cases, as we can see from the above table, temp rise is considerably higher for unplated connections than it is for plated ones. Because bare copper oxidizes very rapidly producing copper oxides which are of very high resistance, leading to high temp rise. This is why terminals & joints are almost universally plated.
The two materials commonly used for plating are silver and tin. The low- voltage switchgear standard IEEE C.37.20.1-1993 speaks of “silver-surfaced, tin surfaced or equivalent” connections.
Now the question arises which one is better between silver and tin. Silver (Ag) has atomic no of 47 while that of Tin (Sn) is 50. If we look into the atomic configuration of Copper (Cu), Silver (Ag) & Tin (Sn) –
Cu – 2+8+18+1
Ag – 2+8+18+18+1
Sn – 2+8+18+18+4
We can easily see that Copper and Silver has identical configuration. Both are having single lone electron in the outermost orbit, leading to very conductive nature. If we look at the conductance values of them at 20 deg.C –
Ag – 6.30 x 10E7 S/m
Cu – 5.96 x 10E7 S/m
Al – 3.5 x 10E7 S/m
Sn – 0.917 x 10E7 S/m
Clearly as we can see, Silver has the highest conductance value amongst all. The higher the conductivity the lesser the heating and lower temp rise. Tin, having the lowest conductivity, lead to high temperature rise.
Again due to its orbital configuration, Tin is easy to be oxidized. Tin oxides (SnO, SnO2) are resistive in nature. Hence they further reduce the conductivity leading to very high temperature rise.
On the other hand, Silver, apart from having high conductivity is also harder than Tin and withstands the stress of a moving joint better than tin.
Hence for various technical and manufacturing reasons, it is not practical to go for tin plating instead of silver plating on surfaces within the circuit breakers or on the circuit breaker terminals. If the atmosphere attacks silver surfaces, they should be coated with contact lubricating grease to prevent corrosion problems.
Aluminium and copper joints are to be done carefully mainly because if such joints are exposed to mist, saline and pollution, the aluminium part commences corroding first as it is more anodic than copper. With the formation of a certain amount of aluminium oxide, copper becomes anodic to aluminium oxide layer and it starts corroding as well. Also, different co-efficient of thermal expansion of these two materials causes the joints to loosen over a period of time in case of cyclic loading.
| Terminal capacity without spreader terminals | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Rating (A) | 16-100 | 125-250 | 320-630 | 800-1250 | |||||
| dsine | Frame | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) |
| DN0 | 35 | <17 | |||||||
| DN1 | 120 | <26 | |||||||
| DN2 | 95 | 25 | |||||||
| DN3α | 185 | <32 | |||||||
| DN3 | 120 | 27 | |||||||
| DN4 | - | 2 * 40 | |||||||
| Terminal capacity with spreader terminals | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Rating (A) | 16-100 | 125-250 | 320-630 | 800-1250 | |||||
| dsine | Frame | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) | Cable (mm2) | Link (mm) |
| DN0 | 50 | 22 | |||||||
| DN1 | 185 | 35 | |||||||
| DN2 | 185 | 35 | |||||||
| DN3α | 2 * 240 | 2 * 40 | |||||||
| DN3 | 2 * 240 | 2 * 40 | |||||||
| DN4 | 2 * 300 | 2 * 60 | |||||||
The above table gives you the suitable link and cable size for different frames of different d-sine MCCBs that can be used for termination purpose. We recommend Copper termination for efficient and superior performance of MCCBs as well as all the switchgears in the panel. It results in lesser temperature rise and hence increases overall life of the entire electrical equipment.
Maya Pai,
Deputy General Manager - Product Management & MarketingMaya Pai is a seasoned Product Management and Marketing professional with over 10 years of experience in the electrical industry, specializing in low-voltage switchgear and circuit protection solutions. Her expertise lies in Molded Case Circuit Breakers (MCCBs) and DC Portfolio management, encompassing product strategy, portfolio development, market analysis, and customer-centric innovation. She has worked extensively across the product lifecycle, translating evolving market and application requirements into competitive and reliable solutions for power distribution systems. Her experience spans conventional AC protection as well as emerging DC applications, supporting the growing demand for energy storage, renewable energy integration, EV infrastructure, and industrial DC power systems. Through her work and writing, she shares insights on switchgear technologies, circuit protection, DC systems, and the future of efficient, safe, and resilient power distribution.