The primary function of circuit breaker is not only to protect system against fault currents but also to protect conductors against overheating which may result into insulation failure.


In circuit breaker overload & short circuit protections are achieved by releases namely,


  1. Thermal magnetic releases (based on bimetal) OR
  2. Microprocessor based release (current transformer based)


MCCB with Thermal Magnetic release:


In this breaker, in case of overload, temperature of the bimetal increases, bimetal bends, hits the trip plate and there by trips the MCCB. After tripping, a definite time is required for bimetal to cool and come back to a position (not original one) say Ps, trip plate position does not allow breaker to switch ON till this time. Now if an overload occurs, bimetal requires less time to trip the breaker as it is not reached to its original position say Po, hence it has to travel lesser distance to trip (refer fig 1).

Thermal Memory

This inherent characteristic of Bimetal is known as THERMAL MEMORY. This is useful because when overload occurs in cyclic manner, the temperature of the conductor keeps on increasing and the accumulated energy (I2t) also increases (refer fig 2). Hence thermal magnetic release takes less time to trip the breaker and there by reduces the thermal stresses on the system and protects the insulation.

Bimetal

MCCB with Microprocessor based release

In this breaker CTs are used to measure the currents. In case of cyclic overload conditions, release will interpret every pulsating overload of the system as an independent fault and not account for the inherent accumulated energy buildup of the system. Hence breaker release will not trip in less time as there is no physical bimetal and intrinsic thermal memory feature. As a result, thermal stresses on the system will be more. Refer figure 3.

MCCB with Microprocessor

Therefore, in the microprocessor release, thermal memory feature is developed using a capacitor. When overload/short circuit occurs, this capacitor gets charged; release trips the breaker as per the settings (Trip point). The discharge time of this capacitor mimics the cooling time characteristics of the bimetal. Therefore, if the breaker is switched on immediately after fault clearance, charge on capacitor will trip the breaker again. This can be considered as a nuisance tripping. MCCB must be switched on after specific time, say ts when the capacitor would be discharged below a preset level corresponding to position Ps of bimetal and hence enabling the MCCB switching ON without nuisance trip. If overload/short circuit occurs after switching on then MCCB release will trip the breaker in lesser time (as capacitor is not fully discharged) there by reducing the thermal stresses on the system.


Hence inherent feature of a thermal magnetic release is provided in a Microprocessor release by the “Thermal memory” feature.


  • This feature gets activated only in case of LTS is ON
  • This can be enabled or disabled.


In case of RC10/20 MCCBs, when the current through the MCCB exceeds the overload pickup value, a thermal memory capacitor gets immediately charged. Now if the MCCB trips due to overload or short circuit fault, the thermal memory capacitor begins to discharge. Ideally time required for the thermal memory capacitor to discharge (corresponding to position Po of bimetal) completely is 20 minutes (to). Time required (ts) corresponding to position Ps is much lesser than this. Refer fig 4.

MCCB Trips

If thermal memory feature is not available, RC10/20 release will interpret every cyclic overload of the system as an independent fault and not account for the inherent accumulated energy buildup of the system. Hence takes regular time as per the time settings to trip on every pulse and hence will lead to larger system stresses thereby damaging the insulation.


When MCCB is switched ON after tripping on fault, it first monitors


  1. The Overload or LTS status (ON or OFF)
  2. Actual current through breaker (through CT measurement)
  3. The charge across the thermal memory capacitor.


If MCCB is switched ON within 20 minutes after tripping on fault, then


Situation 1: If LTS is ON and there is overloading


The release monitors a non-zero charge across the thermal memory capacitor and it senses the current in the system which is exceeding the Overload setting set by the user, it interprets the system is hot and trips in less time. The trip times are then as per the hot trip time curves as per the design of the internal algorithm.


Situation 2: If LTS is ON and there is no overloading/ short circuit


The release monitors a non-zero charge across the thermal memory capacitor and it senses the current in the system is less than the Overload setting set by the user it allows the MCCB to pass the current without issuing a trip. The thermal memory capacitor discharges to zero value as per the cooling time curve as per the design of the internal algorithm.


Situation 3: If LTS is OFF and there is overloading or no overloading


Thermal memory feature is not active. Also release will not protect against overload as LTS is Off.


Thus a much closer protection of the system is offered to the user in case of thermal memory feature is active.

ReleaseThermal memory- Enabled byThermal memory- Disabled by
RC 10 release by default shorting pins 9 & 10 of test port
RC 20 release by default by menu settings- Thrm: Off
MTX release by separate dip switch by default

About the Author

author

Maya Pai,

Deputy General Manager - Product Management & Marketing

Maya Pai is a seasoned Product Management and Marketing professional with over 10 years of experience in the electrical industry, specializing in low-voltage switchgear and circuit protection solutions. Her expertise lies in Molded Case Circuit Breakers (MCCBs) and DC Portfolio management, encompassing product strategy, portfolio development, market analysis, and customer-centric innovation. She has worked extensively across the product lifecycle, translating evolving market and application requirements into competitive and reliable solutions for power distribution systems. Her experience spans conventional AC protection as well as emerging DC applications, supporting the growing demand for energy storage, renewable energy integration, EV infrastructure, and industrial DC power systems. Through her work and writing, she shares insights on switchgear technologies, circuit protection, DC systems, and the future of efficient, safe, and resilient power distribution.