Default

UW1 1600N 4P100%N MB 3.5

Cat Number
:
 UW116NFB01300

Specifications

General

Short Description
UW1 1600N 4P100%N MB 3.5
Conformity to Standard
IS / IEC 60947 (Part-1 & 2), EN 60947-2, IEC 60695-2-1
Poles
4P
Frame
Frame 1

Electrical Characteristics

Operational Frequency (Hz)
50/60HZ
Rated breaking capacity
50 kA
Rated Current
1600A
Rated impulse withstand voltage (Uimp)
12kV (Main Circuit) & 4kV (Auxiliary Circuit)
Rated insulation voltage (Ui)
1000VAC
Rated making capacity
105 kA
Rated operational voltage (Ue)
415VAC
Short Time Withstand (KA rms) @1sec
50 kA
Release
MTX3.5
Features Fields
CE
Main/Acc/Spare
Main Unit
Operational Features
100%
Protection against Mechanical Impact
IK08 Standard, IK10 Optional
Termination capacity
Top Vertical-Bottom Vertical
Utilization Category
B

Environmental Conditions

Degree of protection
IP53 Standard, IP54 Optional
Operating temperature
-25 degC to 70 degC
Protection against Mechanical Impact
IK08 Standard, IK10 Optional

Features

Operational Features
100%
Version
N
Features Fields
CE

Life

Electrical life-Operating Cycles
10000
Mechanical life-Operating Cycles
20000

Termination

Termination capacity
Top Vertical-Bottom Vertical
loader

Assistance Required?

Select an option to Contact Us