Sandwich BBT – Benefits, Types of route, Metering provision

Sandwich BBT – Benefits, Types of route, Metering provision
Updated: | 6 min read

Technical Articles

Table of Contents

Click on any topic to jump to that section

Introduction

Busbar Trunking System (BBT) performs the function of transporting current form one point to the other. Traditionally cables were used for this function. BBT goes beyond what cables do. BBT can tap off power to switchgear for further distribution using Plug-in boxes (PIB) or Tap-off boxes (TOB). In comparison to cables, PlB/TOB of BBT can thus serve as distribution panels at different stages (e.g. at floors of a building). BBT thus continues as single systems to replace cables as well as incomer distribution boards at floor level for building (Residential or commercial). The BBT system offer a superior alternative to cables and other bus trunking options through this compact and scalable range of system thus providing an enhanced solution to power transmission and distribution in buildings as well as industry. The below mentioned table shows the advantages of using a Busduct system over the cable system.

Table 1 – Technical Comparison of Sandwich busduct Vs Cables
FactorCableBBTComparison
Safety Less More SC withstand capacity, Protection against fire
Space required Large Small Single run for multiple circuits
Flexibility to Requirements No Yes Load can be added and adjusted on the existing system
Service Life Low High Average service life is >20 years
Mechanical Strength Low High Metal Enclosure
Installation Cost High low Shorter installation time, less support and space required
Maintenance Cost High low Maintenance free system
Aesthetics Poor Good Compact in size and well finished surface

A Busduct System is an assembly comprising a system of conductors with one or more bars separated or / and supported by insulating material and contained in a conduit or similar casing. There are mainly two types of busduct systems based on the type of construction: Air-insulated and Sandwich.


An air-insulated busduct construction has air as an insulation between conductors, hence the overall size of this type of busduct is more compared to a sandwich busduct.


A Sandwich Busbar Trunking System (BBT) is manufactured as a totally enclosed, pre-fabricated sections consisting of copper or aluminum busbars.


Power is simply tapped off by PIB / TOBs positioned at required intervals. A sandwich busduct system will consist of Straight lengths (Power transmission & distribution), Flange ends (for incoming connection), Elbows (for routing direction), End feed box (for isolation between cables & BBT), End cover (for terminating the route), PIB/TOB (for distribution) and other accessories. The below mentioned table shows the comparison of Sandwich type BBT v/s Air Insulated BBT

Table 2 – Technical Comparison of Sandwich busduct Vs Air Insulated busduct
Sandwich BusductAir Insulated Busduct
Compact Size Size typically more than 3 times of Sandwich Busduct
Don’t have air gap and tested for fire related tests Enclosure with large air gap hence fire can spread easily due to chimney effect
Joints are with single bolt. Quick installation possible Joints are made with multiple bolts, takes longer time for installation
Less installation material & cost More installation material & cost
Plug-in type boxes can be installed & removed easily; even when riser is Live Bolt-on type boxes takes longer time; not possible to install when riser is Live
Higher fault level withstand capacity Much limited fault level withstand capacity due to supports construction
Lesser voltage drop @0.8 p.f. Higher voltage drop @0.8 p.f.

As we can see from above the sandwich busbar trunking system has several key advantages over conventional forms of power distribution:

  • Reduced on-site installation time when compared to a cable system, leading to cost savings.
  • Increased flexibility in design and versatility for future modifications compared to cable & Air insulated busduct systems.
  • Increased safety features brought about by the use of high-quality manufactured components.


Sandwich busbar trunking system (BBT) is a compact design and an efficient, safe and ideal system for power distribution to industrial installations and high rise building structures, offering a wide current range from 250A to 6300A in Aluminum / Copper conductors. Power can be tapped by means of PIB / TOB fitted with SCPD (16A - 1250A). The system can have a provision of maximum 5 Plug-in outlets combined on both sides per 3 meters length, which can be fitted quickly and provides total flexibility for any change in distribution layout.


Tap-off Units (TOU): There are 2 types of TOUs:

  • Plug-in Box (PIB) – With spring loaded jaw contacts and are removable type - available from 16A to 400A. This can be used in Building & Industrial application
  • Tap-off Box (TOB) – With fixed / bolted type arrangement are generally used for higher ratings distribution 630A to 1250A. Due to its better contact resistance, it can also be used in industries for Welding applications


II. Sandwich busbar trunking system (BBT) - Insulation Class:


Various kinds of insulating materials are used in Sandwich type BBTs. The commonly used Insulation are Class-B (130°C) and Class-F (155°C).


Many times it is observed that various class of insulation are combined to achieve higher class but as per standard when various class of Insulation are combined the insulation of lowest class is only considered.


Sandwich BBT need to comply with Clause No. 10.10 of IEC 61439-1 / 6 which states the temperature rise limits permissible for Copper BBT over an ambient of 35°C which are indicated below (Source: IEC 61439-1 Table No-6 & IEC 61439-6)

Table 3 – Temperature rise limit for Copper & Aluminum Busbar
Temperature limitCopperAluminium
Enclosure 55°C 55°C
Termination 70°C 70°C
Joint/Busbar 105°C 90°C

Considering the ambient temperature of 35°C as per IEC 61439 standard, temperature rise allowed on Joints is 105°C that means total temperature can go up to 140°C (35+105) in case of Copper busduct and up to 125°C (35+90) in case of Aluminium busduct, hence Class-B insulation will not withstand the full temperature in case of Copper busduct and has very limited buffer in case of Aluminium busduct, whereas Class-F insulation will have safer buffer of 15°C (155°C-140°C) even in case of Copper busduct.

III. Sandwich busbar trunking system (BBT) - Layouts / Routes:


Following are the types of BBT layouts;

Transformer / DG to LV Panels: One of the most frequently used routes. It connects the Transformer / DG to LV Panel. It is usually a simple route with very less complications. Majority of the times this route will be IP66 (outdoor) type with canopy since the transformer is placed in an open area.


LV Inter Panel Connection: It connects the outgoing feeder of 1st panel to incoming of 2nd panel. This route will be indoor (IP4X/5X) since LV panels will be kept in dedicated rooms. This is also referred as Feeder busduct and has no tapping points.

 Transformer to LV Panel Layout

Methods of LV Power Distribution:


Horizontal Power Distribution: This method is normally used in industries, Data centers, warehouses where power received from BBT is horizontally distributed in different sections. Power distribution system routes will be installed indoor and it can possibly have multiple Tap-off points in segments like industries, Data centers, etc. throughout its length.

Inter Panel Connection

Vertical Power Distribution (Riser): This method is used in high rise residential / commercial office or IT buildings where power received from BBT is vertically distributed in different outgoing feeders at floor level. This route will be installed in electrical shaft and it will have multiple Tap-off points at floor levels.

Horizontal Power Distribution

2 ways in which vertical riser arrangement can be achieved;


  • Directly from LT Panel: This is the regularly used method where there are less towers in same complex and distribution run is not long.
  • End Feed Unit (EFU): This is used when there are multiple towers in same complex and distribution run is very long. Before EFU there will be cable run and then BBT will start only in the electrical shaft from EFU.
Directly from LT Panel
End Feed Unit

IV. BBT Metering Provisions:


We have seen the ways how power can be distributed horizontally & vertically. In industries, Data centers power is rarely monitored at each Tap-off unit level, but in case of Residential or Commercial buildings it is required to monitor the Power for each tenant. Power monitoring is possible in Busduct routes using Meters in different ways. Following are the methods used for metering;


Commercial Buildings: In commercial buildings, metering is generally used by single entity who is the owner/developer and the tenants pay utility bills to owner/developer. The owner/developer pays the single energy bill to the utility service provider for the actual consumption. To ensure that all the required cost incurred is taken into account owner/developer uses an energy monitoring system in their premises.


BBT is used In Commercial installations for providing power to entire floor or divide the same to each client if needed on each floor. In this, normally sub metering is done and hence utility meters are rarely used but on the contrary panel mounted meters are preferred which are communication capable.


Normally these meters communicate on RS-485. It is also possible to integrate the metering in BBT Tap-off units as seen below. The advantage of metering inside TOU is that it saves space for additional metering panel.

TOB with meter (left) and Metering Room (right)

In recent times, a new trend of Franchisee metering is observed where in the infrastructure would be provided by the developer, billing is directly charged and paid by the tenant to the utility. Further, there would likely be a separate arrangement between the utility provider and the developer.


Residential Buildings: In residential buildings, metering is normally done by utility company and hence metering is in utility company’s scope. Following methods of power distribution are generally used in residential buildings. Meters are used with CT.


  • Common Metering Room at single floor – Although often used method when cables were used, this method is rarely used when we use BBT. In this method, there is a common metering panel on ground floor / basement level and the BBT with TOU is used for 5-10 floors or as per the capacity of loads to be fed or space in shaft to mount a TOU. Cabling has to be done from the TOU to meter and back to the tenant main Distribution board. This method is not cost effective and is space consuming.
  • Metering provision at refuge floor – In this scheme, meter is made at every refuge floor which connects tenant meters of specific floors which are located together (e.g. 0-7 floors, 8-14 floors). As per the capacity of loads fed rating of PIB/TOB will be selected. The advantage with this method is all electrical components like meters, SCPD are located in refuge area room and facilitates utility person in energy management and maintenance. However, the cost of cabling in this method is comparatively lesser than earlier option.
TOB (left) and Metering Room (right)
  • Metering provision at every floor: This method is currently the most popular method and used in most of the high rise buildings. In this method, metering is done on each floor inside the shaft. Floor wise required power is tapped from the TOU thru meter, protected on either sides by SCPD and then distributed to the tenants flat. Here the meters used have a provision of communication and the schemes for metering (non wired / wired / smart) are provided by the utility company. BBT should have multiple Tap-off points to offer redundancy. Its advantage is that it is easy to install, manage and comparatively cost competitive solution.
 PIB and Metering panel inside shaft

Conclusion

From the above note, it is clear that Sandwich type BBT is more preferred over conventional methods of cables and Air Insulated busducts as it offers safer, reliable and energy efficient power distribution solution.


Sandwich type BBT as a system is very efficient which provides more safe, convenience and reliable power distribution vis-à-vis other power distribution systems.


Sandwich busducts can be used in various segment applications with different type of layout and even metering is possible with different options.

About the Author

author

Sourav Dasmodak,

Product Management & Marketing (Powergear - ACB)

Product Owner of Air Circuit Breaker (ACB) of Lauritz Knudsen for Domestic & International Market. I can talk to you about Electrical Products' Sales, Business Development, Market Expansion, Cracking Critical Strategic Account, handling Key Account & of course how to develop & motivate Channels along with the organizational growth. Having near about one and a half decade of experience across the country with major electrical manufacturers (Top 4).

Assistance Required?

Select an option to Contact Us

contact-sales
Contact Sales
product-sales
Contact Support