General
Short Description
Motorised COSD Frame 4-400A-240V a.c.
Conformity to Standard
IS / IEC 60947-3, EN 60947-8
Internal Accessories
Terminal Shroud,Phase Barriers,Source Separator
External Accessories
CK90192OOOO ATC2000OOOO CK90099OOOO CK90195OOOO
Electrical Characteristics
Operating Time( I-O-II)
<1.4 sec
Operating Time( I-O/II-0)
0.7 sec
Short Circuit Making Capacity
46 kA RMS
Operational Frequency (Hz)
50/60 Hz
Rated breaking capacity@AC-23A
3200A
Rated impulse withstand voltage (Uimp)
12kV
Rated insulation voltage (Ui)
1000V
Rated making capacity@AC-23A
4000A
Rated operational current at 415V
400A
Rated Operational Power (kW)
225
Rated operational voltage (Ue)
415V
Short Time Withstand (KA rms) @1sec
22
Accessories
CK90192OOOO,ATC2000OOOO,CK90099OOOO,CK90195OOOO
Mounting positions
Universal
Operating Time( I-O-II)
<1.4 sec
Operating Time( I-O/II-0)
0.7 sec
Short Circuit Making Capacity
46 kA RMS
Standard Accessories
Terminal Shroud,Phase Barriers,Source Separator
Suitable for isolation
Yes
Utilization Category
AC-23A
Environmental Conditions
Ambient temperature
-5 ˚C to 55 ˚C
Features
Mounting positions
Universal
Standard Accessories
Terminal Shroud,Phase Barriers,Source Separator
Suitable for isolation
Yes
Utilization Category
AC-23A
Mounting positions
Universal
Life
Electrical life-Operating Cycles
2000
Mechanical life-Operating Cycles
10000
Physical Dimensions
Termination
Terminal capacity
2 x 300 sq.mm
Container Information
Package Level 1 Width
420
Package Level 1 Height
430
Package Level 1 Depth / Length
0.62