Default
FN 100 A SDF IN NEW ENCL
Cat Number
:
 SK90485OOOO
Switch Disconnector Fuse is combination of a disconnector and fuses. These are capable of making, carrying and breaking currents under normal circuit conditions which may include specified operating overload conditions and because of fuses mounted on SDF, these can break abnormal currents such as those of short-circuit.

Specifications

General
Short Description
FN 100 A SDF IN NEW ENCL
Conformity to Standard
IS60947-3, IEC60947-3 & EN60947-3
Poles
3P
Frame
Frame 2
Electrical Characteristics
Operational Frequency (Hz)
50 / 60Hz
Rated breaking capacity(A)
800A
Rated Conditional SC Current
100kA
Rated Current
100A
Rated impulse withstand voltage (Uimp)
8kV
Rated insulation voltage (Ui)
690VAC
Rated making capacity(A)
1000A
Rated making capacity@AC-23A
1000
Rated operational current at 415V
100
Rated operational voltage (Ue)
415VAC
Rated Voltage
415VAC
KVAR
36
Environmental Conditions
Ambient temperature
40
Degree of protection
0
IP Rating
0
Operating temperature
-20 to 50 degree Celcius
Pollution Degree
3
Features
Enclosure
No
Fuse Type
DIN
Utilization Category
AC-23A
Life
Mechanical life-Operating Cycles
15000
Physical Dimensions
Height
448
Width
330
Depth
245
Termination
Maximum Al cable with lug (sq mm)
95
Terminal capacity
95mm Main, 50 mm neutral
Maximum Al cable with lug (sq mm)
95
Tightening Torque
4
loader

Assistance Required?