Default
UW1 2000H 4P100%N MD 4.5 VV
Cat Number
:
 UW120HFD01500

Specifications

General
Short Description
UW1 2000H 4P100%N MD 4.5 VV
Conformity to Standard
IS / IEC 60947 (Part-1 & 2), EN 60947-2, IEC 60695-2-1
Poles
4P
Frame
Frame 1
Electrical Characteristics
Operational Frequency (Hz)
50/60HZ
Rated breaking capacity
80 kA
Rated Current
2000A
Rated impulse withstand voltage (Uimp)
12kV (Main Circuit) & 4kV (Auxiliary Circuit)
Rated insulation voltage (Ui)
1000VAC
Rated making capacity
176 kA
Rated operational voltage (Ue)
415VAC
Short Time Withstand (KA rms) @1sec
80 kA
Release
MTX4.5
Environmental Conditions
Degree of protection
IP53 Standard, IP54 Optional
Operating temperature
-25 degC to 70 degC
Protection against Mechanical Impact
IK08 Standard, IK10 Optional
Features
Operational Features
100%
Utilization Category
B
Version
H
Life
Electrical life-Operating Cycles
10000
Mechanical life-Operating Cycles
20000
Physical Dimensions
Height
433
Width
447
Depth
421
Weight
127
Termination
Termination capacity
Top Vertical-Bottom Vertical
Termination capacity
Top Vertical-Bottom Vertical
loader