Default
MCCB dsine DZ6-400L 400A 3P 120kA iTRP1
Cat Number
:
 DZ6T0400LXF1AOOOO

Specifications

General
Short Description
MCCB dsine DZ6-400L 400A 3P 120kA iTRP1
Conformity to Standard
IS60947-2, IEC60947-2 & EN60947-2
Poles
3P
Frame
DZ6
Electrical Characteristics
Operational Frequency (Hz)
50/60 Hz
Rated breaking capacity
120kA
Rated Current
400A
Rated impulse withstand voltage (Uimp)
8V
Rated insulation voltage (Ui)
1000
Rated operational voltage (Ue)
800
Rated Service circuit breaking capacity
100%
Release
iTRP1
Environmental Conditions
Ambient temperature
-25°C to 55°C for TM and -25°C to 75°C for ETU
IP Rating
IP40 and IP54 with Extended ROM
Pollution Degree
III
Features
Load-line bias
No
Release Type
LS/IN
Suitable for isolation
Yes
Utilization Category
A
Life
Electrical life-Operating Cycles
8000
Mechanical life-Operating Cycles
20000
Physical Dimensions
Height
205
Width
120
Depth
105
loader